6.

Installation of Wired Controller

No.
1
Socket's base box
Description
installed in the
wall
Fig.4: Sketch for Installation of Wired Controller. Pay attention to the following items during
installation of wired controller:
1. Cut off power supply of heavy-current wire embedded in mounting hole in the wall before
installation. It is prohibited to perform the whole procedure with electricity.
2. Pull out 4-core twisted pair line in mounting hole and then make it through the rectangle hole at
the back of controller's soleplate.
3. Joint the controller's soleplate on wall face and then fix it in mounting hole with screws M4X25.
4. Insert the 4-core twisted pair line through rectangle hole into controller's slot and buckle the
front panel and soleplate of controller together.
5. At last, fix the controller's front panel and soleplate with screws ST2.2X6.5.
Caution:
During connection of wirings, pay special attention to the following items to avoid interference of
electromagnetism to unit and even failure of it.
1. To ensure normal communication of the unit, signal line and wiring (communication) of wired
controller should be separate from power cord and indoor/outdoor connection lines. The distance
between them should be kept 20cm in min.
2. If the unit is installed at the place where there is interference of electromagnetism, signal line
and wiring (communication) of wired controller must be shielded by twisted pair lines.
Fig.4 Sketch for Installation of Wired Controller
2
Soleplate of
Screw
controller
M4X25
10
3
4
Front panel of
controller
5
Screw ST2.2X6.5

Advertisement