Rack-Mounting Procedures At A Glance - H3C S6820 Series Installation Manual

Hide thumbs Also See for S6820 Series:
Table of Contents

Advertisement

Figure 11 Mounting brackets and grounding cable installation positions on the S6820-4C
switch
(1) Auxiliary grounding point 2
(3) Primary grounding point
(5) Auxiliary grounding point 1

Rack-mounting procedures at a glance

Figure 12 Rack-mounting procedure
NOTE:
If a rack shelf is available, you can put the switch on the rack shelf, slide the switch to an appropriate
location, and attach the switch to the rack with the mounting brackets.
Follow these guidelines when you install the switch in a 19-inch rack:
The distance between the front and rear posts of the rack must meet the requirements
described in
To secure the switch to the rack, you must install not only mounting brackets, but also chassis
rails and slide rails.
Table 4 Distance requirements between the front and rear rack posts
Switch
model
S6820-32H
Table
4.
Installation method
Using the mounting brackets and
long slide rails (provided)
Using the mounting brackets and
short slide rails (optional)
1
2
3
(2) Power module-side mounting position
(4) Port-side mounting position
Minimum distance
between the front
and rear rack posts
621 mm (24.45 in)
401 mm (15.79 in)
9
5
4
Maximum distance
between the front
and rear rack posts
934 mm (36.77 in)
714 mm (28.11 in)