58 Installing the 8010co chassis
To attach a ground to one of the chassis grounding studs, you need the
following:
The figure
59)
this example, each chassis is configured with three 8004DC power supplies.
Your rack-grounding strip may look different or may be in a different location
than the one shown in the example.
The table
grounding" (page 59)
"Chassis and 8004DC power supply grounding example" (page
Installing and Maintaining the Ethernet Routing Switch 8000 Series Chassis
Copyright © 2007, Nortel Networks
.
one single-hole cable lug that fits over one of the grounding studs
a nut and a locking washer for the grounding stud
6 AWG grounding wire that is long enough to connect to the ground point
7/16-in. hex wrench to fasten the hardware in the correct order
"Chassis and 8004DC power supply grounding example" (page
shows an example of how to ground two 8010co chassis and a BIP. In
"Item description for chassis and 8004DC power supply
describes the reference items shown in the figure
Nortel Ethernet Routing Switch 8600
NN46205-303 01.01 Standard
4.1 2 January 2007
59).