Siting And Transport Requirements; Transport; Installation Room Requirements - Viessmann Vitocal 300-G Series Installation And Service Instructions Manual

Heat pump with electric drive
Table of Contents

Advertisement

Siting and transport requirements

Transport

For handling purposes, the heat pump module can be
removed: See page 69.
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never put weight on the top, front or side panels
of the appliance.

Installation room requirements

!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
The installation room must be dry and free from
the risk of frost:
Ensure ambient temperatures between 0 and
35 °C.
Max. 70 % relative humidity (corresponds to
an absolute humidity of approx. 25 g water
vapour/kg dry air)
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take the
total weight of the appliance into account.
Total weight
Type
Weight in kg
BW
301.A21
301.A29
301.A45
Type
Weight in kg
BWS
301.A21
301.A29
301.A45
To prevent the transmission of structure-borne noise,
never site the appliance above ceilings with wooden
joists, e.g. in the attic.
!
Please note
Tilting the compressor at a steep angle inside
the heat pump can result in appliance damage.
Max. tilting angle: 45° for a very short time
Minimum room volume (to EN 378)
Type
BW
301.A21
BWS
301.A29
301.A45
Minimum clearances for 1-stage (type BW 301.A)
≥ 400
Fig. 3
245 kg
272 kg
Clearance subject to on-site installation and site
A
298 kg
conditions
Note
240 kg
Observe clearances for installation and mainte-
267 kg
nance.
293 kg
Additional strain relief clamps are required for the
power cables if the clearance behind the heat pump
is more than 80 mm.
Preparing for installation
Refrigerant
Minimum
charge in kg
room volume
in m
3
4.7
6.2
7.7
A
≥ 400
10.7
14.1
17.5
11