Commissioning, inspection, maintenance
Commissioning the system
Adjust values for Vitovent 200-W/300-C/300-W if necessary
Parameter
"Ventilation"
Ó
"Set room temperature C108"
"Background ventilation C109"
"Reduced ventilation C10A"
"Standard ventilation C10B"
"Intensive ventilation C10C"
"Background ventilation, second fan duct C189"
(Vitovent 200-W only)
"Reduced ventilation, second fan duct C18A" (Vitovent 200-W
only)
"Standard ventilation, second fan duct C18B" (Vitovent 200-W
only)
"Intensive ventilation, second fan duct C18C" (Vitovent 200-W
only)
Parameters for ventilation with Vitovent 300-F
Parameter
"Ventilation"
Ó
"Vitovent enable 7D00"
Further enabling for Vitovent 300-F if necessary
Parameter
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"Enable reheater bank hydraulic 7D02"
"Enable humidity sensor 7D05"
"Enable CO2 sensor 7D06"
"Type of heat exchanger 7D2E"
Adjust values for Vitovent 300-F if necessary
Parameter
"Ventilation"
Ó
"Set room temperature 7D08"
"Flow rate reduced ventilation 7D0A"
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Parameters for utilisation of power generated on site
Parameter
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"Threshold for electrical power 7E04"
58
(cont.)
Setting
Max. 4 K higher or lower than "Stand-
ard room temperature 2000" (adjust-
ment value: 1
Subject to sizing
Setting
"1" Vitovent 300-F
Setting
"1"
"1"
"1"
"1"
"0" Countercurrent heat exchanger
"1" Enthalpy heat exchanger
Setting
"100" to "300" (
Subject to sizing
Setting
"1"
"0" to "300" (
0.1 °C)
Ventilation unit service instruc-
tions
10 to 30 °C)
Ventilation unit service instruc-
tions
0 to 30 kW)