Electrical connection
Terminals
Function
F1
Fuse 6.3 A (slow)
X1
Earth conductor X1.
X2
Neutral conductor X2.N
X3
Power supply terminals of control
unit "L1" and auxiliary components
Switched phase L1:
X3.1, X3.2, X3.3, X3.7, X3.11,
X3.13
X3.1
Switched phase
X3.2
"External blocking" signal: External
X3.14
blocking of compressor and pumps,
mixer in control mode or CLOSE
X3.3
Flow switch
X3.4
X3.6
Power-OFF
X3.7
G
(cont.)
?
Explanation
Note
Observe the total load 1000 W of all connected compo-
nents.
Terminals for earth conductor of all associated system
components
Terminals for neutral conductor of all associated sys-
tem components
Terminals for signal and safety connections
Switched phase L1:
Switched phase can be used for on-site system com-
ponents.
Observe the total load 1000 W of all connected com-
ponents.
Requires floating contact:
Closed: Power-OFF enabled
Open: No power-OFF
Breaking capacity 230 V~, 2 mA
Note
The system may no longer be protected against frost.
These and further external functions (e.g. provision of
external set values) can alternatively be connected
via the external EA1 extension.
See "EA1 extension" installation instructions
Requires floating contact:
Closed: Heat pump in operation
Open: Heat pump shut down
Breaking capacity 230 V~, 0.15 A
Jumper is used in some devices.
No jumper should be installed if a flow switch is con-
nected.
Requires floating contact:
Closed: No blocking (safety chain continuous)
Open: Blocking enabled
Breaking capacity 230 V~, 0.15 A
Installation sequence
29