Optimization Functions; Type Of Optimization - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Settings
Caution
Room model
Settings
170/232
Building Technologies
HVAC Products
10.7

Optimization functions

The optimization functions are activated or influenced by the following settings:
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit > Optimizations / Influences
Operating line

Type of optimization

Forward shift on max
Early shutdown max
Quick setback
[Boost heating] setpoint increase
Room temperature rise
10.7.1 Type of optimization
The type of optimization decides whether the optimization functions and boost heating
shall be performed based on the acquired room temperature or whether the room
model shall be used.
In plant where the heating circuit operates in connection with a ventilation system as a
room control combination, the room temperature sensor of the ventilation plant must
not be located in the extract air!
Based on the outside temperature, the building time constant and the rate of room
temperature increase, the room model calculates the room temperature.
If no room temperature sensor is connected, the optimization functions can work with
this room model.
TR
Cmf
TRM
TRw
Economy
T
Room model temperature
RM
TRw
Room temperature setpoint
In the case of sudden positive increases of the room temperature setpoint, the room
model temperature is updated at the rate of room temperature increase. In the case of
sudden negative drops, the room model temperature approaches the composite outside
temperature at 3 times the building time constant, whereby the process is stopped as
soon as the current room temperature setpoint is reached.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit > Optimizations/influences
Operating line
Type of optimization
Boiler Sequence Controller RMK770
10 Heating circuit control
Range
With room model / With
room temp sensor
0...48 h
00.00...06.00 h.min
Off / On
--- / 0...20 K
1...600 min/K
t
Range
With room model / With
room temp sensor
Factory setting
With room model
6 h
00:00 h.min
On
5 K
60 min/K
Factory setting
With room model
CE1P3132en