Advertisement

Load reduction
Load increase
Settings
Building Technologies
HVAC Products
Operating line
Actuator running time
P-band Xp
Integral action time Tn
For more detailed information about mixing valve control and its setting aids, refer to
section 5.7 "Mixing valve control".
9.6.2

Load control

The heat output of mixing valve control can be reduced by functions of higher priority
(e.g. by return temperature limitation) or by functions of other plants (boiler, DHW
heating). This is accomplished via load control.
T
T
Heat
source
Heat
consumer
Load reduction can be triggered by one of the following functions:
• Protective boiler startup
• Limitation of the return temperature
• DHW heating with shifting priority
• DHW heating with absolute priority
From the consumer's point of view, a load increase can be effected in the form of pump
and / or mixing valve overrun. In principle, this means load maintenance.
9.7

Optimization functions

The opimization functions are activated or influenced by the following settings:
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit 1 (or 2 or 3 ) > Optimizations/influences
Operating line
Type of optimization
Forward shift on max
Early shutdown max
Quick setback
[Boost heating] setpoint increase
Room temperature rise
Modular Heating Controller RMH760B
9 Heating circuit control
Range
1...600 s
1...100 K
0...600 s
T
Heat
consumer
Range
With room model /
With room temp sensor
0...48 h
00.00...06.00 h.min
Off / On
0...20 K
1...600 min/K
Factory setting
150 s
50 K
60 s
Heat demand
Load control
Factory setting
With room model
0 h
00:00 h.min
On
5 K
60 min/K
131/238
CE1P3133en