12.4

Display inputs

On the RMK770, 4 universal inputs can be defined for display purposes.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line
Display input 1
Display input 2
Display input 3
Display input 4
The type or unit of the display input can be selected with the input identifier.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line
Display input 1
Display input 2
Display input 3
Display input 4
For detailed information about resolution, type of sensor, etc., refer to subsection 3.4.7
"Configuration of the universal inputs and outputs".
The type of input can be selected. In the case of an analog input, it is the type of input,
and in the case of a digital input, the normal position.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Inputs > ...X...
Operating line
Type reference
Value low
Value high
Correction
Normal position
The inputs can be assigned free text (maximum 20 characters).
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Texts
Operating line
Display input 1
Display input 2
Display input 3
Display input 4
For more detailed information about the configuration of analog inputs, please refer to
subsection 3.4.7 "Configuration of the universal inputs and outputs".
Boiler sequence controller RMK770
12 Function block "Miscellaneous"
Adjustable values / remarks
Assign terminal
Assign terminal
Assign terminal
Assign terminal
Range
°C / % / g/kg / kJ/kg /
W/m2 / m/s / bar / mbar
/ Pa / ppm / Universal
000.0 / Universal 0000 /
Digital
Like display input 1
Like display input 1
Like display input 1
Range
Ni1000 / 2×Ni1000 / T1
/ Pt1000 / 0...10 V
Depending on the
selected type
Depending on the
selected type
–3.0...+3.0 K
Open / Closed
Range
Max. 20 characters
Same as display input 1
Same as display input 1
Same as display input 1
Factory setting
°C
°C
°C
°C
Factory setting
Ni1000
Depending on
the type
Depending on
the type
0.0 K
Open
Factory setting
193/232
CE1P3132en
23.04.2009