The Composite And The Attenuated Outside Temperature - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Attenuated outside
temperature
Heating curve
Other influences
Composite outside
temperature
Outside temperature
p
= 50%
Window
Building Technologies
HVAC Products
To determine the heating limit (summer / winter operation), the attenuated outside
temperature is required (refer to section below).
The heating curve is defined by the 2 curvepoints at the design temperature and the
theoretical heating limit. Heat transmission in the space is not linear, however. When
the difference between flow temperature and room temperature is small, the rate of
heat transmission diminishes. This is considered by the heating curve.
The setpoint predefined by the heating curve can additionally be influenced by the
following factors:
• Room temperature setpoint
• Current room temperature (room temperature influence)

10.5.1 The composite and the attenuated outside temperature

Identifiers used:
To
Outside temperature
Toeff
Outside temperature
Tofil
Outside temperature filtered with the building time constant
ToStrDmp
Outside temperature
τ
Bldg
Building time constant
p
Proportion of windows in %
Window
The composite outside temperature is made up of the current outside temperature To
and the outside temperature Tofil filtered with the building time constant
proportion of windows p
with which the 2 temperatures are considered.
The composite outside temperature is used for the heating curve and the heating limit.
To obtain the attenuated outside temperature, the actual outside temperature To is
filtered twice with the building time constant
To
τ
Bldg
For the heating limit, the actual, the composite and the attenuated outside temperature
are considered.
The controller is supplied with the proportion of windows set to 50% so that the com-
posite outside temperature represents the mean value of actual and filtered outside
temperature.
It is calculated as follows:
Toeff = (0.5 × To) + (0.5 × Tofil)
Boiler sequence controller RMK770
10 Heating circuit control
(adjustable from 0 to 100%) determines the proportions
Window
τ
Bldg.
+
p
Window
100
100-p
Window
100
Tofil
τ
Bldg
τ
Toeff
+
ToStrDmp
Bldg. The
163/232
CE1P3132en
23.04.2009