Addendum; Configuration Diagrams; Terminal Markings; Code Letters - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Use
Uppercase letters
Lowercase letters
218/232
Building Technologies
HVAC Products
16

Addendum

16.1

Configuration diagrams

Use of the configuration diagrams is explained in subsection 3.3.5 „Use of configuration
diagrams"

16.1.1 Terminal markings

The designations of the signal inputs and outputs and of the assigned connection
terminals are structured according to the following pattern:
Example
Explanation
N.X3
N = controller RMK770
X3 = universal input
N.D1
N = controller RMK770
D1 = digital input
A9(2).Y1
A9 = type of extension module
(2) = 2nd extension module of the same type
Y1 = analog output DC 0...10 V
N.Q7
N = controller RMK770
Q7 = relay output

16.1.2 Code letters

Physical inputs and outputs are marked with uppercase letters:
Code letter
Explanation
N
Boiler sequence controller RMK770
A5
Universal module RMZ785
A7
Universal module RMZ787
A7
Universal module RMZ788
A9
Universal module RMZ789
D
Digital input
X
Universal input
Q...
Switching load (changeover or NO contact)
Y
Analog output DC 0...10 V
3P
3-position output in pairs
Internal signals are marked with lowercase code letters:
Code letter
Explanation
x
Analog or digital
a
Analog
d
Digital
i
Pulse

16.1.3 Configuration choices

A maximum of 3 extension modules with outputs for 7 single or twin pumps as well as
7 positioning outputs are available. The procedure for the configuration is always as
follows:
• from arrow
to line
• from uppercase to uppercase letter
• from lowercase to lowercase letter
Boiler Sequence Controller RMK770
16 Addendum
CE1P3132en
23.04.2009