The temperature request for the current heat demand is calculated based on the flow
temperature setpoint of the heating circuit (refer to subsections 10.5.2 "Heating curve"
and 10.5.3 "Influence on the flow temperature setpoint") plus an adjustable setpoint
increase for the mixing valve.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit > Mixing circuit controller
Operating line
Setp increase mixing valve
Setpoint increase mixing valve is used to define by what amount the temperature
request (to the boiler or the primary controller) shall be raised against the flow tempera-
ture setpoint.

10.10 Extra functions

10.10.1 Text designations

Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit
Operating line
Heating circuit
Time switch
The texts entered here appear on the menu and on the info display in place of the initial
texts.

10.10.2 Acquisition of the room temperature

For the optimization functions and/or the influence on the flow temperature setpoint, the
room temperature is required.
The input is configured via the extra configuration:
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs > Room sensor
Assign terminal
A heating circuit can handle a maximum of 2 room temperatures. It is of no importance
whether the room temperature is acquired locally or via KNX bus.
The average is generated from the 2 actual values.
Boiler sequence controller RMK770
10 Heating circuit control
Range
0...50 K
Range
Max. 20 characters
Max. 20 characters
Factory setting
10 K
Factory setting
Heating circuit