Holiday/special day
Calendar operation: Master
Calendar zone: 1
14.3

Room data

Every heating circuit belongs to a geographical zone. The zone represents the room to
be controlled. Within the zone, the data related to the room are exchanged:
• The room operating mode
• The room temperature
• The setpoints

14.3.1 Communication variants

The requirements (operation, function) placed on the generation of the room operating
mode vary considerably, depending on the type of building and building usage. The
communication variants described below make it possible to match the room operating
mode to the relevant requirements.

14.3.2 Settings

Main menu > Commissioning > Communication > Room heating circuit
Operating line
Geographical zone (apartment)
Time switch slave (apartment)
Time switch operation
The settings made are also displayed under:
Main menu > Device information > Communication > Heating circuit
The geographical zone from which a value is received and the geographical zone to
which a value is sent must be selected.
Within the geographical zone, the heating circuits forward:
• The room temperature (actual value and setpoint)
• The time switch data
• The room operating mode
If a heating circuit sends data to other rooms, assignment to the respective geographi-
cal zone must be correctly set.
Heating circuits with the setting "Room control combination" = slave (refer to subsection
10.10.3 "Room control combination") receive the room temperature (actual value and –
possibly – the setpoint) and the room operating mode from the room control master of
the same geographical zone.
Time switch data are sent only if operating line "Time switch slave (apartment)" is set to
"----", that is, when the controller is the time switch master.
Boiler Sequence Controller RMK770
14 Communication
Holiday/Special day
Calendar operation: Slave
Calendar zone: 1
Range
---- / 1...126
---- / 1...126
Autonomous / Slave /
Master
Factory setting
----
----
Display only