Types Of Primary Controller; Control Of Mixing Valve; Pump Control - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Heat requests
Fault setting
primary controller
Building Technologies
HVAC Products
The heat requests can be received from other devices via bus. In addition, there are 3
binary inputs and 1 analog input for signalling heat requests.
9.3

Types of primary controller

If only a pump or twin pump is configured, the primary controller consists of system
pump control. If, in addition, a mixing valve is configured, the primary controller consists
of mixing circuit control plus pump or twin pump control.
Y1
B1
M1
B7
Primary controller type 1:
With mixing valve
B1
Flow temperature sensor (* = optional, for display only)
B7
Return temperature sensor (* = optional, for display only)
M1
System pump (can be a twin pump)
Y1
Mixing valve
Primary controller type 1 with mixing circuit can provide optional maximum limitation of
the return temperature while primary controller type 2 only controls a system pump
depending on demand.
The flow or return temperature sensor of primary controller type 2 can be used for
display purposes.
By configuring the outputs, it is defined whether a primary controller type 1 or type 2 is
used. Without configuration of a mixing valve, type 2 is automatically used. It is also
possible to define a flow temperature boost with the type 2 controller to compensate for
temperature losses in the case of long pipes.
9.3.1

Control of mixing valve

For control of the mixing valve, a 3-position or DC 0...10 V actuator can be used. The
selection is made by configuring the relevant output.
9.3.2

Pump control

Pump control offers a number of monitoring choices, no matter if it is a single or twin
pump.
For more detailed information about pump control and twin pumps, refer to section 5.8
"Pump control".
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Primary controller > Fault settings > Overload pump
Operating line
Fault acknowledgement
Fault acknowledgement B
Boiler sequence controller RMK770
9 Precontrol
B1*
M1
B7*
Primary controller type 2:
With system pump
Range
None / Acknowledge /
Acknowledge and reset
None / Acknowledge /
Acknowledge and reset
Factory setting
Acknowledge
Acknowledge
139/232
CE1P3132en
23.04.2009