● The sampling times (p0115[0] and p4099) of all components that are connected to a DRIVE-
To enable the function "Automatic configuration" to assign the encoders to the drives, the
recommended rules below must be observed.
Recommended rules
● The DRIVE-CLiQ cable from the Control Unit must be connected as follows:
● The DRIVE-CLiQ connections between the power units must each be connected from
Figure 5-2
● The motor encoder must be connected to the associated power unit.
Component
Single Motor Module booksize
Double Motor Module booksize
Single Motor Module chassis
Power Module chassis
PPU
Manual, 01/2014, 6FC5397-2DP40-3BA3
CLiQ line must be divisible by one another with an integer result. If the current controller
sampling time on a DO has to be changed to another pattern that does not match the other
DOs on the DRIVE-CLiQ line, the following options are available:
– Reconnect the DO to a separate DRIVE-CLiQ line.
– Also change the current controller sampling time and the sampling time of the inputs/
outputs of the DO not involved so that they again fit into the time grid.
Note
A Double Motor Module, a DMC20, and a TM54F each correspond to two DRIVE-CLiQ
nodes. This also applies to Double Motor Modules, of which just one drive is configured.
– To X200 of the first booksize power unit
– To X400 of the first chassis power unit
interface X201 to X200 or from X401 to X400 on the follow-on component.
Example: DRIVE-CLiQ line
Rules for permitted topologies
5.2 Topology rules for S120 Booksize
Connecting the motor encoder via DRIVE-CLiQ
X202
● Motor connection X1: Encoder at X202
● Motor connection X2: Encoder at X203
X402
X402
57