7.7 PP 72/48D 2/2A PN
Table 7-104 Overview of messages as a function of the "alive and well" counter
"alive and
well" counter
0
1
2
3 ... 7
Table 7-105 Elimination of error at "alive and well" counter status "2"
Value
Cause
byte 1
1
In the temperature
measurement operating
mode, an input voltage is too
high. The hardware may
become damaged/
destroyed as a result.
2
Reserved
3
Overload at the outputs
4
Incorrect operating mode
selection, e.g. temperature
measurement at the analog
outputs.
5
Internal error, system error
6
Overrange at the inputs
7
Overrange at the outputs
The analog outputs retain their last specified value.
1)
Diagnostics via Status Bytes 0/1
In Status Byte 0, the set operating modes are reflected e.g. "0x55" if Control Byte 0 = 0x55
has been specified.
In the event of an error, the error bit is set in Status Byte 1 (bit 7). In the event of an error in
one channel, all channels are disabled.
206
Value
Message
byte 1
0
Reserved
Temperature value
0
No error
1
Impermissible input voltage in temperature measurement mode
2
Reserved
3
Overload at the outputs
4
Incorrect operating mode selection
5
Internal error, system error
6
Overrange at the inputs
7
Overrange at the outputs
0
Reserved
Effect
The "PNFault" LED is activated.
The outputs are disabled.
The value 0x80 is stored in Status Byte
1.
-
The "PNFault" LED is activated.
The outputs are disabled.
The value 0x80 is stored in Status Byte
1.
Selection of operating mode is rejected,
The "PNFault" LED is activated.
The outputs are disabled.
The value 0x80 is stored in Status Byte
1.
Remedy
It is essential that a Pt100 element is
connected to terminals 3-4 or 7-8.
1)
The module must be restarted with
Power ON following elimination of the
error.
-
Check the loads at the analog output.
The module must be restarted with
1)
Power ON following elimination of the
error.
If selected correctly, the module switches
to cyclic operation.
The firmware has detected a system
error, this status can only be exited by
1)
means of a switch-on / switch-off.
Check input circuit and adjust, if required.
Correct values in the user program.
Manual, 01/2014, 6FC5397-2DP40-3BA3