Siemens SINUMERIK 828D PPU Series Manual page 234

Hide thumbs Also See for SINUMERIK 828D PPU Series:
Table of Contents

Advertisement

Spare parts and accessories
9.3 SENTRON PAC3200/PAC4200
Parameter
Measuring inputs for voltage
3 AC; UL-L/UL-N; CAT III
● Wide-range power supply
Measuring inputs for voltage
3 AC; UL-L/UL-N; CAT III
● Low-voltage power supply
Measurement at voltage transformers for
voltages > 500 V / 690 V
Measuring inputs for current
3 AC; CAT III
Current direction
programmable
Measurement using current transformers
Dimensions (W x H x D)
Overall depth
● Without module
● With module
Protection class
Degree of protection at front
Slots for expansion modules
Operating temperature
Relative humidity in operation
at 25° C without condensation
Degree of contamination
Approvals
Further information
You can find additional information on the Internet at:
● SENTRON PAC3200 (http://support.automation.siemens.com/WW/view/de/25240652)
● SENTRON PAC4200 (http://support.automation.siemens.com/WW/view/de/31675630)
234
SENTRON PAC3200
Max. 690 V / 400 V
95 to 240 VAC 50/60 Hz ±10%
110 to 340 VDC ±10%
Max. 500 V / 289 V
22 to 65 VDC; ±10%
x/1 A or x/5 A
96 x 96 x 56 mm
51 mm
73 mm
1
-10 to +55° C
CE, cULus, C-Tick, GOST
Manual, 01/2014, 6FC5397-2DP40-3BA3
Value
SENTRON PAC4200
✓ per phase
96 x 96 x 82 mm
77 mm
99 mm
II
IP65
2
95 %
2
CE, cULus, GOST
PPU