Troubleshooting Suggestions - Wells GK48 Owner's Manual

Ventless universal hood system for electric cooking appliances
Table of Contents

Advertisement

TROUBLESHOOTING SUGGESTIONS

Problem
Unit will not operate (no
indicators lights lit)
Unit will not operate
(buzzer sounds)
CHECK FILTER light lit
REPLACE FILTER light lit
SERVICE REQUIRED
light lit (cooking appliance
not operating)
NOTE:
FILTERS are the only user serviceable components in this ventilator hood system. For all problems that cannot be remedied by
servicing the filters, contact:
Ventilator section - authorized Wells service agency
Fire suppression system - authorized Ansul® distributor
Ansul Deployments are not covered under warranty. Technical service needs to be contacted immediately and a deployment kit of
parts needs to be replaced before unit is put back in service. WS-WL0964 DEPLYMNT KIT, WVU-48
IMPORTANT:
Contact ANSUL® for fire suppression system installation, set-up and service:
Ansul Incorporated
One Station Street
Marinette, WI 54143-2542 website http;//www.ansul.com
IMPORTANT:
Parts used in the Ansul® fire suppression system are not serviceable by the owner/operator.
Procedures for servicing fire suppression equipment are described in:
ANSUL® R-102 SYSTEM DESIGN, INSTALLATION, RECHARGE AND MAINTENANCE MANUAL
(418087, current edition)
NOTE:
ANSUL® Manual 418087 is intended for use by authorized Ansul® service personnel only.
Possible Cause
Disconnected from electric power
Fire suppression system not set
Filter pack, Pre-filter or baffle filter not in position
Filter nearing end of service life
Filter pack plugged
Fire damper in exhaust collar has closed
One or more vacuum sensing lines or ports
plugged, or sensing line dislodged.
NOTE: If, after 20 seconds, there is insufficient airflow for proper operation, SERVICE REQUIRED
light will illuminate and under-hood appliance (s) will be de-energized.
Press VENTILATOR POWER SWITCH to OFF, then back to ON to reset system.
1-800-TO-ANSUL (1-800-862-6785)
Reconnect to electric power
Reset circuit breaker for unit
Contact an authorized Ansul®
distributor for repairs
Properly install filters
Arrange to replace filters in a timely manner
Replace filter pack
Contact an authorized Wells service
agent for repairs
Contact an authorized Wells service
agent for repairs
42
Suggested Remedy

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wvu48Wvu96Gk96

Table of Contents