● STARTER does not display any screen forms.
● Adjustable parameters cannot be changed using commissioning tools, e.g. an operator
panel or Startdrive.
When know-how protection is active, support can only be provided (from Technical Support)
after prior agreement from the machine manufacturer (OEM).
Adjustable parameters that can be changed when know-how protection is active
Several adjustable parameters can be read and changed when know-how protection is
active. You can find a list of the adjustable parameters that can be read and changed in the
List Manual under "KHP_WRITE_NO_LOCK".
In addition, you can define an exception list of adjustable parameters, which end users may
change.
Adjustable parameters that can be read when know-how protection is active
Several adjustable parameters can be read but not changed when know-how protection is
active. You can find a list of the adjustable parameters that can be read in the List Manual
under "KHP_ACTIVE_READ".
Functions that are inhibited when know-how protection is active
Active know-how protection inhibits the following functions:
● Download of inverter settings using STARTER or Startdrive
● Automatic controller optimization
● Stationary or rotating measurement of the motor data identification
● Deleting the alarm history and the fault history
● Generating acceptance documentation for the safety functions
Functions that can be executed when know-how protection is active
The following functions can be executed when know-how protection is active:
● Restoring the factory setting
● Acknowledging faults
● Displaying faults, alarms, fault history and alarm history
● Reading out the diagnostic buffer
● Controlling the inverter via the control panel in STARTER or Startdrive
● Uploading adjustable parameters that can be changed or read when know-how protection
is active
● Displaying the generated acceptance documentation for the safety functions
Depending on the know-how protection settings, the trace function in STARTER can also be
active when know-how protection is active.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Backing up data and series commissioning
8.5 Write and know-how protection
191