Advanced commissioning
7.15 Motor temperature monitoring using a temperature sensor
Parameter
p0610
p0640
p4621
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.
168
Description
Motor overtemperature response (factory setting: 12)
Determines the inverter behavior when the motor temperature reaches the alarm
threshold p0604.
0: Alarm A07910, no fault.
1: Alarm A07910 and fault F07011. The inverter reduces its current limit.
2: Alarm A07910 and fault F07011.
12: Alarm A07910 and fault F07011. For use of the thermal motor model in parallel to
the temperature sensor: After switching off the supply voltage, the inverter saves the
most-recently calculated difference to the ambient air temperature. After switching the
supply voltage on again, the thermal motor model starts with 90% of the previously
saved difference temperature.
Current limit [A]
Motor temperature sensor configuration
.00
0 signal: Enable PTC short-circuit monitoring
1 signal: Disable PTC short-circuit monitoring
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE