Table 7- 7
Response, if the inverter has executed the change request
Data block
Header
Table 7- 8
Response if the inverter was not able to completely execute the change request
Data block
Header
Values, parameter 1
Values, parameter 2
...
Values, parameter m
Error values
Table 7- 9
Error value in the parameter response
Error
Meaning
value 1
00 hex
Illegal parameter number (access to a parameter that does not exist)
01 hex
Parameter value cannot be changed (change request for a parameter value that cannot be changed)
02 hex
Lower or upper value limit exceeded (change request with a value outside the value limits)
03 hex
Incorrect subindex (access to a parameter index that does not exist)
04 hex
No array (access with a subindex to non-indexed parameters)
05 hex
Incorrect data type (change request with a value that does not match the data type of the parameter)
06 hex
Setting not permitted, only resetting (change request with a value not equal to 0 without permission)
07 hex
Descriptive element cannot be changed (change request to a descriptive element that cannot be changed)
09 hex
Description data not available (access to a description that does not exist, parameter value is available)
0B hex
No master control (change request but with no master control)
0F hex
Text array does not exist (although the parameter value is available, the request is made to a text array that
does not exist)
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257324B AE
Byte n
Reference (identical to a change request)
01 hex (ID of drive objects, at G120 al-
ways = 1)
Byte n
Reference (identical to a change request)
01 hex (ID of drive objects, at G120 al-
ways = 1)
Format
40 hex: Zero (change request for this data
block executed)
44 hex: Error (change request for this data
block not executed)
Only for "Error" - error value 1
You can find the error values in the table at the end of this section.
Only for "Error" - error value 2
Error value 2 is either zero, or it contains the number of the first index where the error oc-
curred.
...
...
...
7.4 Drive control via PROFIBUS and PROFINET
Bytes n + 1
02 hex (change request successful)
Number of parameters (identical to a change
request)
Bytes n + 1
82 hex: (Inverter was not able to completely
execute the write request)
Number of parameters (identical to a change
request)
Number of error values
00 hex
01 hex or 02 hex
Advanced commissioning
101
n
0
2
n
0
2
4
6
8
...