The Tamper condition is reset when the Keypad is closed and Tamper condition is reset.
Supervise:
1.
2.
3.
5.7.4

Keypad lock out

Condition:
Invalid code is entered more times than allowed by the code retry attempts (programmed in
location 179)
Restore:
Keypad lock out is reset when the Keypad lockout time (3min) is expired and the fault is reset.
Supervise:
1.
2.
3.
5.7.5

Sensor Tamper

Condition:
Tamper contact is triggered (Zone is programmed as Dual End of Line)
Restore:
Tamper contact is restored and Tamper condition is reset.
Supervise:
1.
2.
3.
Sensor Tamper Zone Indication
The zone indicator 5 lights to indicate Sensor Tamper conditions.
Enter [5] to step to Zone Indicator list to identify the Zone where the Sensor Tamper comes
from.
1=Zone 1 2=Zone 2 3=Zone 3 4=Zone 4 5=Zone 5 6=Zone 6 7=Zone 7 8=Zone 8
5.7.6

Zone Tamper

Condition:
Tamper contact (direct connected to the Zone) is triggered (Zone type = Tamper)
Restore:
Tamper contact is restored and Tamper condition is reset.
Supervise:
1.
2.
3.
Bosch Sicherheitssysteme GmbH
Report the Tamper condition to configured destination on Location 140 when the
Tamper Condition is detected.
Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
When the Tamper Condition is reset, send the restored report to the configured
destinations. The FAULT indicator is turned off when there is no other system fault.
Report the Keypad lock out to configured destination on Location 140 when the Keypad
lock out is detected.
Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
When the Keypad lock out Condition is reset, send the restored report to the configured
destinations.The FAULT indicator is turned off when there is no other system fault.
Report the Sensor Tamper to configured destination on Location 140 when the Sensor
Tamper is detected.
Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
When the Tamper condition is reset, send the restored report to the configured
destinations. The FAULT indicator is turned off when there is no other system fault.
Report the Tamper condition to configured destination on Location 140 when the
Tamper condition is detected.
Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators).
When the Tamper condition is reset, send the restored report to the configured
destinations. The FAULT indicator is turned off when there is no other system fault.
Installation Manual