Bosch Option Bus Power Supply Fail

Condition:
Bosch option bus power supply Voltage is lower than 9V+-5%.
Restore:
Voltage is raised to 12.5V+-5% and fault is reset.
Supervise:
1.
2.
3.
4.
5.2.5

RF Power Supply Fail

Condition:
Voltage is lower than 4V+-5%.
Restore:
Voltage is raised to 5.5V+-5% and fault is reset.
Supervise:
1.
2.
3.
4.
5.3

Warning Device Failure

The zone indicator 3 lights to indicate Warning Device Failure. Enter [3] to step to external
modules fail list for more information.
5.3.1

Warning Device 1 Disconnected

Condition:
Warning Device is disconnected.
Restore:
Warning Device is connected and fault is reset.
Supervise:
1.
2.
3.
Bosch Sicherheitssysteme GmbH
Monitor the voltage by MPU.
Report the AUX power fault to the configured destination programmed on location 140.
Slow flash FAULT indicator (refer to the detailed description in chapter keypad
indicators)
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
Monitor the voltage by MPU.
Report the Bosch Option Bus Power Supply fault to the configured destination
programmed on location 140.
Slow flash FAULT indicator (refer to the detailed description in chapter keypad
indicators)
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
Monitor the voltage by MPU.
Report the RF power fault to the configured destination programmed on location 140.
Slow flash FAULT indicator (refer to the detailed description in chapter keypad
indicators)
When the fault is reset, send the restored report to the configured destinations. The
FAULT indicator is turned off when there is no other system fault.
Monitor the voltage by MPU.
Report the siren fault to the configured destination programmed on location 140
Slow flash FAULT indicator (refer to the detailed description in chapter keypad
indicators)
Installation Manual
Fault and Tamper Description | en
F.01U.241.127 | V4 | 2011.12