8. Install a mounting screw into each of the open mounting holes aligned with the rack, starting from the
bottom.
9. Visually inspect the alignment of the services gateway. If the services gateway is installed properly in
the rack, all the mounting screws on one side of the rack should be aligned with the mounting screws
on the opposite side and the services gateway should be level.

Install the Services Gateway Without a Mechanical Lift

Lifting the chassis and mounting it in a rack requires at least two people. The empty chassis weighs
approximately 65.5 lb (29.7 kg).
1. Ensure that the rack is in its permanent location and is secured to the building.
2. Position the chassis in front of the rack or cabinet, centering it in front of the mounting shelf. Use a
pallet jack if one is available.
3. With one person on each side, hold onto the bottom of the chassis and carefully lift it onto the small
mounting shelf. See
Figure 7 on page
Figure 7: Lift the Services Gateway into the Rack
4. Slide the chassis onto the mounting shelf until the mounting brackets contact the rack rails. The shelf
ensures that the holes in the mounting brackets and the front-mounting flanges of the chassis align
with the holes in the rack rails.