6.2 Group b, Application

b1- 00
Frequency Command Selection 1
Selects the frequency command source for the REMOTE mode.
Note:
When the run command is input with 0 Hz frequency command or below the minimum frequency, the RUN
LED will blink.
No.
b1-00
0 : Keypad
Allows two ways to input the frequency command.
Switching between the multi-step speed command in parameters L1-□□ (by digital input
terminal).
Entering the frequency command on the keypad.
1 : Control Circuit Terminal (Analog Input)
Allows a voltage or current input as analog frequency command from terminal A1.
□ Voltage Input
Allows a voltage signal input via terminals A1. Refer to Table 6.4 for parameter settings.
Signal
Terminal
Level
0 to 10 V
A1
-10 to 10 V
b1: Operation Mode Selection
Name
Frequency Command Selection 1
Table 6.4 Frequency Command Using Voltage Signals
Parameter Settings
Signal Level
Function Selection
Selection
E3-00 = 2
(Main Frequency Command)
E3-00 = 3
E3-01 = 0
45
Setting Range
0 to 3
Gain
Bias
Ensure DIP switch A1 is
E3-02
E3-03
placed to V (voltage)
Default
0
Notes