Sets the cooling fan off-delay time when P7-03=0 that the drive waits to disabled the cooling
fan after run command is released.
No.
P7-04
P7-05
Ambient Temperature Setting
Sets the ambient temperature. This automatically decreases the drive rated current when the
ambient temperature is higher than the temperature specified in drive specifications. The
installation method is required to be set in P7-12.
No.
P7-05
P7-12
Installation Method Selection
Selects the installation type. The drive overload detection limit will be changed according to
the selection.
Note:
1. This value cannot be reset by A1-03 (Reset).
2. The default value is preset to the appropriate value. Do not change this value unless using side-by-side
installation or mounting the drive with the heatsink outside the cabinet.
No.
P7-12
0 : IP20 Enclosure in a Cabinet
Select this when the IP20 enclosure drive is installed in a cabinet with at least 30 mm room to
the next drive or a cabinet wall.
1 : Side-by-Side Mounting
Select this when the drive is mounted side-by-side with 2 mm to 29 mm room to the next
drive.

6.8 Group o, Keypad Function Settings

o1 Display Setting
o1- 00 Frequency Command Setting/Display
o1-00 used to select the frequency command unit and monitor values. o1-00 = 3 and under
Name
Heatsink Cooling Fan Off-Delay Time
Name
Ambient Temperature Setting
Name
Installation Method Selection
Setting Range
0 to 300 s
Setting Range
-10 to 50°
Setting Range
0 to 2
141
Default
60 s
Default
40°
Default <1><2><3>
0