“H6” Compressor Startup Failure - Daikin Altherma EKHBH Series Service Manual

Table of Contents

Advertisement

ESIE06-03
"H6" Compressor Startup Failure
3.11
H6
Error code
Method of
A compressor startup failure is detected by checking the compressor running condition through the
malfunction
position detection circuit.
detection
Malfunction
decision conditions
Supposed causes
Part 3 – Troubleshooting
The compressor fails to start in about 15 seconds after the compressor run command signal is
sent.
Clearing condition: Continuous run for about 5 minutes (normal)
The system will be shut down if the error occurs 8 times.
Compressor relay cable disconnected
Compressor itself defective
Outdoor unit PCB defective
Stop valve closed
Input voltage out of specification
Error Codes: Outdoor Units
3–27
1
3 3
4
5