Removal procedure: outdoor unit ERYQ005~007AAV3
1
Step
Procedure
3
Release the clamp by
pliers to detach the wire
harness for the
compressor.
3
4
Remove the putty.
Before working,
make sure that the
refrigerant is empty
in the circuit.
Be sure to apply
nitrogen
replacement when
heating up the
brazed part.
5
Heat up the brazed
parts indicated by the
5 5
arrows.
5–26
Points
Warning
Ventilate when refrigerant leaks
during the work (if refrigerant
contacts fire, it will cause to arise
toxic gas).
Provide a protective sheet or a
steel plate so that the brazing flame
cannot influence peripheries.
Be careful so as not to burn the
compressor terminals or the name
plate.
Be careful so as not to burn the
heat exchanger fin.
Warning
Since it may happen that
refrigeration oil in the compressor
will catch fire, prepare wet cloth so
as to extinguish fire immediately.