10.1 Cyclic data exchange
10.1.2

Cyclic input data

Cyclic data exchange between the heating control system and the S7 controller takes place
via the process and /I/O address area of the CPU. The cyclic data can be addressed in the
S7 controller through the process image or I/O commands.
Cyclic input data for CIM
Byte
0
1
2, 3
4, 5
6, 7
The measured values represent the measured values of the POM 1.
1
128
Status
Meaning
bit
0
Heater
0: Heating is switched off
1: Heating is switched on
1
Operating mode
0: "Production" mode
1: "Standby" mode
2
Line voltage compensation
0: Is Off
1: Is On
3
0 (not in use)
4
0 (not in use)
5
0 (not in use)
6
0 (not in use)
7
0 (not in use)
0 (not in use)
Measured value
Measured value
Measured value
Line voltage L12 with one decimal place
1
Line voltage L23 with one decimal place
1
Line voltage L31 with one decimal place
1
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005