Communications
10.2 Acyclic data exchange
10.2.2

Acyclic output data

Data record 100 "Field type 1"
The data record describes an HCS function and addresses the HCS.
Byte
0, 1
2, 3
...
124,
125
126,
127
Using this data record, fields of type 1 can be defined. This field type comprises one channel
range that is described by the first and last channel of the field.
Application range:
● Thermoforming
● Clustering of channels that are located next to each other
Definition is via an array [1 to 32] with two elements of type "Word". Up to 32 fields can be
defined.
The field number corresponds to the array index. Field number 0 cannot be used. It exists
automatically in the HCS and contains all the channels of the HCS by default. Production
and standby setpoints are preset to 100%.
All channels that are not explicitly assigned to a new field remain in this default field.
If users want to use fields, they must ensure that all existing channels are assigned to a user
field.
A field can be erased by entering a 0 for the number of the start channel and the end
channel.
Note
If a data record 100 was written, it is no longer possible to use the data records for
field type 2.
132
Meaning
Start channel for field 1
End channel for field 1
...
Start channel for field 32
End channel for field 32
SIPLUS HCS4300 PROFINET/PROFIBUS DP