Configuring/Programming
8.3 Device/hardware configuration in the TIA Portal
8.3.3

Configuration parameters

8.3.3.1

CIM / POM configuration parameters

The configuration parameters are directly assigned to the respective module and are set
during device configuration. The transfer is performed automatically upon start-up and during
re-parameterization.
Configuration parameters CIM
Description
Rated voltage for line voltage
compensation
Configuration control
Configuration parameters POM4320
Description
Control mode
(Set once per POM)
Response to errors
(setting per channel)
86
Value range
360 V to 520 V
No (default)
Yes
Value range
Half-wave control (default)
Half-wave control with soft start variant 1
Half-wave control with soft start variant 2
Half-wave control with soft start variant 3
Phase control
Phase control with soft start variant 1
Phase control with soft start variant 2
Phase control with soft start variant 3
Channel substitute value 0 (default)
Channel value retained
SIPLUS HCS4300 PROFINET/PROFIBUS DP