Expanded I/O Input Data; Support Of Additional Input Data - Siemens SIMATIC ET 200PA SMART Operating Instructions Manual

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

Functions

7.3 Support of additional input data

Parameter assignment / Operation of HART field devices
The following is required for the parameter assignment / operation of HART field devices:
● EDD (for ET 200PA SMART) as of version V1.1.17
EDD (Electronic Device Description) is required to set up HART field devices. It is included
on the
● PDM Version as of V8.2.0.1 with PDM Device Library 1#2014.
See also
S7-300 Automation Systems, ET 200M Ex I/O Modules
support.automation.siemens.com/WW/view/en/1096709)
ET 200M Distributed I/O Device HART Analog Modules
support.automation.siemens.com/WW/view/en/22063748))
7.2

Expanded I/O input data

The IM 650 interface module supports up to 32 bytes of I/O input data.
This function is only available in conjunction with the ET 200PA SMART analog input module
AI16x16Bit.
For the expanded I/O input data (Byte 16...Byte 31), the same system properties apply as for
the "standard" I/O input data (Byte 0...Byte 15). This data is updated at the same rate and has
the same substitute value behavior as the "standard" I/O input data.
7.3
Support of additional input data
The IM 650 interface module supports additional input data, such as the HART primary and
secondary variables provided by HART analog modules from the S7-300 series of modules.
For detailed information, refer to the documentation for the respective HART modules.
● ET 200M Distributed I/O Device HART Analog Modules (http://
support.automation.siemens.com/WW/view/en/22063748)"
Additional output data are not supported.
For the ET 200PA SMART, this means that:
● When the HART analog module is used, the HART secondary variables must be activated
in the parameter assignment dialog of the module.
● The IM 650 supplies the substitute value "0" in the expanded input data of an module that
is starting up or that has been pulled.
72
PDM Device Library CD supplied with PDM.
(http://
(http://
Operating Instructions, 06/2019, A5E34192013-AB
ET 200PA SMART