Siemens SIPLUS HCS Series Operating Instructions Manual page 167

Io systems for heating elements, heating control system
Hide thumbs Also See for SIPLUS HCS Series:
Table of Contents

Advertisement

Article number
Ambient conditions
Ambient temperature during operation
Ambient temperature during stor-
age/transportation
Air pressure acc. to IEC 60068-2-13
Altitude during operation relating to sea
level
Relative humidity
Vibrations
Shock testing
Dimensions
Width
Height
Depth
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
min.
max.
Storage, min.
Storage, max.
Transportation, min.
Transportation, max.
Operation, min.
Operation, max.
Storage, min.
Storage, max.
Installation altitude above sea level,
max.
Operation at 25 ℃, max.
Operation at 50 ℃, max.
Vibration resistance during opera-
tion acc. to IEC 60068-2-6
Vibration resistance during storage
acc. to IEC 60068-2-6
Shock resistance during operation
acc. to IEC 60068-2-27
Shock resistance during storage
acc. to IEC 60068-2-29
13.1 Technical specifications for CIM
6BK1943-1AA00-0AA0
0 °C
55 °C
-25 °C
70 °C
-25 °C
70 °C
860 hPa
1 080 hPa
660 hPa
1 080 hPa
2 000 m
95 %
50 %; 95 % at 25 °C, decreasing linearly to 50 % at 50
°C
10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1 g
5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1 g
15 g / 11 ms / 3 shocks/axis
25 g / 6 ms / 1 000 shocks/axis
56 mm
285 mm
136 mm
Technical specifications
6BK1943-1BA00-0AA0
165

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siplus hcs4300 profinetSiplus hcs4300 profibus

Table of Contents