3.6

I/O modules

3.6.1

PM4000 DI/DO

Function
The I/O module PM4000 DI/DO provides 8 digital outputs and 8 configurable inputs/outputs.
The digital I/O modules are controlled by the S7-CPU using the process image.
NOTICE
The PM4000 DI/DO must not be used for safety-relevant functions.
Design
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
PM4000 DI/DO
Item
Description
Status LEDs
RUN LED lights up green:
Power ON
Initialization status
ERR LED lights up red:
fault
Digital outputs 1 ... 8
LED to display switching status,
one LED each per input/output
LED on: H state
LED off: L state
Digital inputs/outputs 9 ... 16,
switchable per channel