Carrier 48FC Series Controls, Start-Up, Operation And Troubleshooting page 73

Single package rooftop units with systemvu controls version 1.x and puronr (r-410a) refrigerant
Hide thumbs Also See for 48FC Series:
Table of Contents

Advertisement

DISPLAY TEXT
BACNET (cont)
DEVICE RAT
OBJECT ID RAT
COV RAT
DEVICE SPT
OBJECT ID SPT
COV SPT
LOCAL_SHEDL_EDIT
SYSTEM TOUCH
DEVICE INSTANCE
POLLING RATE
SPACE TEMP AI
SPACE RH AI
ZS SENSOR CFG
ZS1 ADDRESS
ZS2 ADDRESS
ZS3 ADDRESS
ZS4 ADDRESS
ZS5 ADDRESS
ZS POLL RATE
ZS UNIT
ZS FRC UNOC ENBL
ZS FRC UNOC DELAY
ZS TLO CONT ENBL
TLO SET DURING OC
ZS UI MODE
NETWORK CHKLIST
DISPLAY SETTINGS
METRIC DISPLAY
LANGUAGE
CONTRAST ADJUST
PASSWORD ENABLE?
VIEW USER PASSWORD
CHANGE USER PASSWORD
QUICK SETUP CONFIG
TIME
DATE
STARTUP DELAY
UNIT CONTROL TYPE
THERMOSTAT TYPE
DIRTY FILTER TIME
HEATING STAGE QTY
VENT METHOD
FREE COOL MAX OAT
FIRE SHUTDOWN SW
QUICK SET CHKLIST
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
EXPANDED DISPLAY TEXT
BACnet network configuration menu
BACnet device for RAT
Object instance for RAT
Change of value for RAT
BACnet device for SPT
Object instance for SPT
Change of value for SPT
Allow Local Sched Edit
System Touch Menu
System Touch Device Inst
System Touch Poll Rate
System Touch AI for SPT
System Touch AI for SPRH
ZS Sensor Configuration
Zone Sensor 1 Address
Zone Sensor 2 Address
Zone sensor 3 address
Zone sensor 4 address
Zone sensor 5 address
Zone sensor poll rate
Zone sensor unit
ZS Force Unoccup enable
ZS Force unocc wt delay
ZS TLO Cont Enable
ZS TLO set during occ
Zone sensor UI Mode
NETWORK SETUP CHECKLIST
User Display Configurations Menu
Metric Display
Display Language Select
LCD Contrast Adjustment
User Password Protection
View User Password Menu
Change User Password Menu
QUICK SETUP CONFIG MENU
Clock Hour and Minute
Current Date
Unit Startup Delay
Unit Control Type
Thermostat Hardware Type
Change Filter Timer
Number of Heating Stages
Ventilation Method
Free Cooling Max OAT
Fire Shutdown Switch
QUICK SETUP CHECKLIST
VALUES
UNITS
0 to 4194303
1610100
0 to 9999
1010
0 to 60
0
0 to 4194303
1610100
0 to 9999
2007
0 to 60
0
Yes/No
enum
No
0 to 4194303
160099
10 to 60
10
0 to 9999
1
0 to 9999
4
0 to 255
255
0 to 255
255
0 to 255
255
0 to 255
255
0 to 255
255
1 to 100
sec
5
0=degrees F
0=degrees F
Yes/No
No
Yes/No
No
Yes/No
No
Yes/No
No
1=Dual Offsets
1=Dual Offsets
0=Undone,
0=Undone
1=Perfom,
2=Done
Yes/No
No
0=English,
0=English
1=Spanish,
2=French,
3=Portuguese
1 to 10
5
Enable/Disable
Enable
xx:xx
MM/DD/YYYY
10 to 600
sec
30
0=TSTAT,
0=TSTAT
1=SPACE SEN,
2=RAT SEN
0=CONV 2C2H,
0=CONV 2C2
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
0 to 9999
hrs
600
0 to 2
2: all except below
0: 50 Series without FIOP heaters
1: 48 Series single phase power,
0=NONE,
0: No FIOP
1=ECON,
1: Economizer FIOP
2=2POS DMPR,
2: Two Position Damper FIOP
3=ERV,
4=ECON ERV
0 to 90
° F
65
0=NORM OPEN,
2: no FIOP
1=NORM CLSD,
0: FIOP
2=NO SWITCH
0=Undone,
0=Undone
1=Perfom,
2=Done
73
DEFAULT
Low Nox Gas Heat,
48FC 04---07 Low Heat,
48FC 05---07 Med Heat,
50GC 04---06 Low Heat,
50GC 04---05 Med Heat,
50GC 04 High Heat 230v 3ph and 460v,
50GC 05 High Heat 230v 3ph,
50GC 06 Med Heat 460v and 575v
POINT
DEVRAT
OBJRAT
COVRAT
DEVSPT
OBJSPT
COVSPT
LCL_EDIT
DEVST
POLLST
AISTSPT
AISTSPRH
ZSADDR1
ZSADDR2
ZSADDR3
ZSADDR4
ZSADDR5
ZSPOLLRT
ZSUNIT
ZSFUNEN
ZSFUNWT
ZSTLOEN
ZSTLSOC
ZSUIM
CHK_NET
DISPUNIT
LANGUAGE
LCD_CONT
PASS_EBL
TIME
DATE
STARTDLY
CTRLTYPE
STATTYPE
FILTLIFE
NUMHSTGS
VENTTYPE
MAXFREET
FIRE_CFG
CHK_QUIK