Carrier 48FC Series Controls, Start-Up, Operation And Troubleshooting page 109

Single package rooftop units with systemvu controls version 1.x and puronr (r-410a) refrigerant
Hide thumbs Also See for 48FC Series:
Table of Contents

Advertisement

TABLE
DISPLAY NAME
UNIT_CFG
Unit Startup Delay
Unit Control Type
0 = Thermostat
1 = Space Sensor
2 = RAT Control
Thermostat Hardware Type
0 = 2 Stage Conventional
1 = 2 Stage Digital
2 = 3 Stage Conventional
3 = 3 Stage Digital
Ventilation Method
0 = None
1 = Economizer
2 = 2--- Position Damper
3 = ERV
4 = Economizing ERV
2--- Pos Damper/ERV Channel
0 = None
1 = MBB RLY11
2 = MBB RLY06
Tstat Adaptive Staging
Change Filter Timer
Test Inactivity Time Out
0 = Disabled
1 = 30 Minutes
2 = 1 Hour
3 = 2 Hours
4 = 4 Hours
5 = 8 Hours
6 = 12 Hours
CCH Max Temperature
Std Barometric Pressure
Linkage Stage inc. time
Unit's Maximum SAT
Auto Clr SAT Limit Fault
Adaptive Temp Comp Start
User TCS Start Bias Time
DMD_CFG
Low Cool Demand On
Medium Cool Demand On
High Cool Demand On
Low Cool Demand Off
Cool Demand Level Up
Low Heat Demand On
High Heat Demand On
Low Heat Demand Off
Heat Demand Level Up
Space Demand Time Guard1
Space Demand Time Guard2
Space Demand Time Guard3
COOL DMD Offset level 1
COOL DMD Offset level 2
COOL DMD Offset level 3
Heat DMD Offset level 1
Heat DMD Offset level 2
Heat DMD Offset level 3
APPENDIX D: SystemVut Controller CCN Tables
Service Config Tables
VALUES
10 to 600
0 to 2
0 to 3
0 to 4194303
0 to 2
Yes/No
0 to 9999
0 to 6
40 to 90
13 to 35
60 to 600
130 to 210
Yes/No
Enable/Disable
0 to 180
--- 1 to 2
0.5 to 20
0.5 to 20
--- 1 to 2
--- 2 to 2
--- 1 to 2
0.5 to 20
--- 1 to 2
--- 2 to 2
60 to 600
0 to 600
5 to 120
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
0 to 99
UNITS
POINT NAME
sec
STARTDLY
CTRLTYPE
STATTYPE
VENTTYPE
EV2PCHAN
ADPTSTAT
hrs
FILTLIFE
TEST_ITO
° F
CCHMAXT
"Hg
STD_BARP
sec
LSTAGINC
° F
UMAX_SAT
SATLACLR
TCS_CFG
min
TCSUBIAS
° F
DMDLCON
° F
DMDMCON
° F
DMDHCON
° F
DMDLCOFF
° F
CDMD_LUP
° F
DMDLHON
° F
DMDHHON
° F
DMDLHOFF
° F
HDMD_LUP
sec
TDMD_TG1
sec
TDMD_TG2
min
TDMD_TG3
° F
CLDOLEV1
° F
CLDOLEV2
° F
CLDOLEV3
° F
HTDOLEV1
° F
HTDOLEV2
° F
HTDOLEV3
109
WRITE STATUS
30
0 = TSTAT
0 = CONV 2C2H
0: No FIOP
1: Economizer FIOP
2: Two Position Damper FIOP
0: No FIOP
2: FIOP
Yes
600
4
65
29.92
180
200
No
Enable
0
0.5
1
1.5
--- 0.5
--- 0.2
0.5
2
--- 0.5
--- 0.2
120
240
10
1
3
5
1
3
5

Hide quick links: