APPENDIX D: SystemVut Controller CCN Tables
TABLE NAME
DISPLAY NAME
SET_PNT
Occupied Cool Setpoint
Occupied Heat Setpoint
Unoccupied Cool Setpoint
Unoccupied Heat Setpoint
Heat--- Cool Setpoint Gap
SPT Offset Range (+/--- )
Occupied SPRH Setpoint
Unoccupied SPRH Setpoint
TABLE NAME
DISPLAY NAME
CTLRID
Device Name:
Description:
Location:
Software Part Number:
Model Number:
Serial Number:
Reference Number:
Setpoint Table
VALUES
UNITS
55 to 80
° F
55 to 80
° F
65 to 95
° F
40 to 80
° F
2 to 10
^F
0 to 5
° F
0 to 100
%
0 to 100
%
Control ID Table
VALUES
UNITS
48_50LC_
text string
text string
CESR131651---XX---XX
2 to 10
0 to 5
0 to 5
118
POINT NAME
DEFAULT
OCSP
78
OHSP
68
UCSP
85
UHSP
60
HCSP_GAP
5
SPTO_RNG
5
SPRH_OSP
55
SPRH_USP
55
POINT NAME
DEFAULT

Hide quick links: