DISPLAY TEXT
CLOCK (cont)
DST STOP MONTH
DST STOP WEEK
DST STOP DAY
DST MINS TO SUB
START TIME IN DAY
SCHEDULES
SCHEDULE NUMBER
OCCUPANCY SCHEDULE
Holiday adjustment Menu
ALLOW G. HOLIDAY?
TIMED OVR LENGTH
CAN CANCEL T.OVR
UNIT CONFIGURATIONS
GENERAL
STARTUP DELAY
UNIT CONTROL TYPE
THERMOSTAT TYPE
VENT METHOD
2POS/ERV CHANNEL
ADAPTIVE TSTAT
DIRTY FILTER TIME
TEST MODE TIMEOUT
CCH MAX TEMP
STD BARO PRESSURE
LINK STAGEUP TIME
UNIT'S MAX SAT
AUTO SAT FAULTS?
ADAPTIVE TCS?
USER TCS BIASTIME
SWITCH INPUTS CONFIGS
FIRE SHUTDOWN SW
HUMSTAT CHANNEL
HUMSTAT SW TYPE
APPENDIX A: SystemVut Controller Display
Settings Main Menu Layout (cont)
EXPANDED DISPLAY TEXT
Clock Adjustment Menu
DST Stop Month
DST Stop Week
DST Stop Day
DST Minutes to Subtract
Time in day to start DST
Schedules Adjustment Menu
CCN Schedule Number
OCCUPANCY SCHEDULE DATA
Holiday adjustment Menu
Accept Global Holidays?
Timed Override Duration
Allow SPT Ovrd Cancel
Unit Configurations Menu
General Unit Configurations Menu
Unit Startup Delay
Unit Control Type
Thermostat Hardware Type
Ventilation Method
2--- Pos Damper/ERV Channel
Tstat Adaptive Staging
Change Filter Timer
Test inactivity time out
CCH Max Temperature
Std Barometric Pressure
Linkage Stage inc. time
Unit's Maximum SAT
Auto Clr SAT Limit Fault
Adaptive Temp Comp Start
User TCS Start Bias Time
DI Config Menu
Fire Shutdown Switch
Humidistat Status Chan.
Humidistat Switch Type
VALUES
UNITS
1=JANUARY,
2=FEBRUARY,
3=MARCH,
4=APRIL,
5=MAY,
6=JUNE,
7=JULY,
8=AUGUST,
9=SEPTEMBER,
10=OCTOBER,
11=NOVEMBER,
12=DECEMBER
1 to 5
1=MONDAY,
2=TUESDAY,
3=WEDNESDAY,
4=THURSDAY,
5=FRIDAY,
6=SATURDAY,
7=SUNDAY
0 to 90
min
0 to 600
min
0 = Always Occupied,
1--- 64 = Local Schedule,
65--- 99 = Global Schedule
Yes/No
0 to 4
hrs
Yes/No
10 to 600
sec
0=TSTAT,
1=SPACE SEN,
2=RAT SEN
0=CONV 2C2H,
1=DIGI 2C2H,
2=CONV 3C2H,
3=DIGI 3C2H
0=NONE,
1=ECON,
2=2POS DMPR,
3=ERV,
4=ECON ERV
0=NONE,
1=MBB RLY11,
2=MBB RLY06,
Yes/No
0 to 9999
hrs
0=Disabled,
1=30 minutes,
2=1 hour,
3=2 hours,
4=4 hours,
5=8 hours,
6=12 hours
40 to 90
° F
13 to 35
Hg
60 to 600
sec
130 to 210
° F
Yes/No
Enable/Disable
0 to 180
min
0=NORM OPEN,
1=NORM CLSD,
2=NO SWITCH
0=None,
1=MBB DI12,
2=MBB DI13.
3=MBB DI14,
4=MBB DI02,
5=MBB Y3
0=NORM OPEN,
1=NORM CLSD,
64
DEFAULT
POINT
11
STOPM
1
STOPW
7
STOPD
60
MINSUB
120
DST_TOD
0 = Always Occupied
SCHEDNUM
No
HOLIDAYT
4
OTL_CFG
No
CLROVCFG
30
STARTDLY
0=TSTAT
CTRLTYPE
0=CONV 2C2H
STATTYPE
0: No FIOP
VENTTYPE
1: Economizer FIOP
2: Two Position Damper
FIOP
0: No FIOP
EV2PCHAN
2: FIOP
Yes
ADPTSTAT
600
FILTLIFE
4
TEST_ITO
65
CCHMAXT
29.92
STD_BARP
180
LSTAGINC
200
UMAX_SAT
No
SATLACLR
Enable
TCS_CFG
0
TCSUBIAS
2: no FIOP
FIRE_CFG
0: FIOP
0: No Humidi--- MiZer
HUMDCHAN
FIOP
5: Humidi--- MiZer FIOP
0=NORM OPEN
HUMD_CFG