POINT DESCRIPTION
2--- Pos Damper/ERV relay
2Position/ERV Relay Test
A051 Cmp off expected ON
Act Mech Disconnect Alrt
Air Quality CO2 Alerts
Alarm Output Relay State
Alarm Output Relay Test
Alarm Reporting Enable
ALC Auto Id Scheme
All Heat Stages Lockout
AUTO INDEPENDENT TEST
BACnet BMS Schedule
BACnet ID Auto ID
BACnetCal Object Status
Bad DD Point--- OutOfRange
CA1 DDF Fault
CA1 FTP alert
CA1 Rev Rotation alert
CCH Relay 1 State
Cir A DDF Fault
Cir A HDP alert
Cir A HPS alert
Cir A LDP Alert
Cir A LSP Alert
Cir A Press Ratio Alert
Cir A SSP out Rng Alert
Cir.A High Pressure Sw
Circ A SDP Open Alert
Circ A SDP range alert
Circ A SDP Short Alert
Circ A SSP Open Alert
Circuit A CMP A1 Loader
Circuit A Compressor 1
Circuit A Locked Out
Circuit A SSP Shrt Alert
Ckt--- A low charge fault
Clear Alarm History
Cmp Bump Loader Test
COFS Switch State
Compressor A1 Available
Compressor A1 Locked Out
Compressor Alerts
Compressor Bump A1 Test
CompressorStuck on Fault
Condensate Ovrflow fault
CoolDemandLimiting
Cooling Liq Valv Test
Cooling Liq Valve CirA
Cooling W/Comp.A1 Test
Cooling W/Comp.ALD Test
Crankcase Heater 1 test
Currently Occupied
Damper fdbk out of range
Damper fdbk Short Alert
Damper Not Mod Alert
Damper Stuck Closed Alrt
Damper Stuck Open Alert
Diff. Dry Bulb Control
Diff. Enthalpy Control
dirty filter alert
Dirty Filter Alerts
Dmpr fdbk Open Cir Alert
Dry Bulb Lockout
DST allowed?
APPENDIX E: BACnet Points List
Binary Value (BV) Points
POINT ACCESS
UNITS
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
READ ONLY
R/W
READ ONLY
R/W
R/W
R/W
R/W
READ ONLY
R/W
R/W
R/W
R/W
R/W
R/W
R/W
READ ONLY
R/W
R/W
R/W
R/W
READ ONLY
READ ONLY
READ ONLY
R/W
R/W
R/W
R/W
R/W
READ ONLY
READ ONLY
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
BACnet OBJECT
BACnet ID
NAME
erv_2pos
BV:6002
s_erv2p
BV:457
a_caoff
BV:181
a_dnmemd
BV:218
co2s_al
BV:307
equip_alarm
BV:7048
s_alarm
BV:70
ALARMEN
BV:27
auid
BV:106
allhtloc
BV:122
autoindp
BV:163
bms_sced
BV:108
bac_auid
BV:107
calobjst
BV:110
f_bad_dd
BV:243
f_ca1ddf
BV:178
a_ca1ftp
BV:182
a_ca1rr
BV:179
cch_relay
BV:3
f_caddf
BV:168
a_cahdp
BV:172
a_cahps
BV:171
a_caldp
BV:236
a_calsp
BV:170
a_capr
BV:169
a_badspa
BV:189
circa_hps
BV:4
a_opndpa
BV:191
a_baddpa
BV:183
a_shtdpa
BV:202
a_opnspa
BV:200
cmpalena
BV:9
cmpa1ena
BV:5
ciralock
BV:128
a_shtspa
BV:211
f_caloch
BV:167
alarm_hist_clear
BV:32
s_bmpald
BV:64
condensate_switch
BV:7028
ca1_aval
BV:123
ca1_lock
BV:124
comp_alarm
BV:312
s_bmpa1
BV:71
f_cstuck
BV:241
f_cofs
BV:273
cooldmdLimit
BV:435
s_clv_a
BV:456
clv_a
BV:7052
s_coola1
BV:74
s_cola1d
BV:79
s_cchr1
BV:73
occ_status
BV:2008
a_badec1
BV:184
a_shtec1
BV:203
a_dnm
BV:215
a_dnm_sc
BV:216
a_dnm_so
BV:217
dif_db_ena
BV:41
dif_enth_ena
BV:42
a_dfilt
BV:214
filter_alarm
BV:7017
a_opnec1
BV:192
db_lock_out
BV:40
dst_cfg
BV:93
126
CCN POINT
VALUE RANGE
EQUIVALENT
0 TO 1
ERV_2POS
0 TO 1
S_ERV2P
0 TO 1
0 TO 1
1
0 TO 1
CO2S_AL
0 TO 1
ALMOUT
0 TO 1
S_ALARM
0 TO 1
ALARMEN
0 TO 1
AUID
0 TO 1
ALLHTLOC
0 TO 1
AUTOINDP
0 TO 1
BMS_SCED
0 TO 1
BAC_AUID
0 TO 1
CALOBJST
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
CCHR1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
CIRA_HPS
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
COMP_ALD
0 TO 1
COMP_A1
0 TO 1
CIRALOCK
0 TO 1
0 TO 1
0 TO 1
ALHISCLR
0 TO 1
S_BMPALD
0 TO 1
COFS
0 TO 1
CA1_AVAL
0 TO 1
CA1_LOCK
0 TO 1
COMP_AL
0 TO 1
S_BMPA1
0 TO 1
0 TO 1
0 TO 1
CDMLMOFF
0 TO 1
S_CLV_A
0 TO 1
CLV_A
0 TO 1
S_COOLA1
0 TO 1
S_COLALD
0 TO 1
S_CCHR1
0 TO 1
OCCUPIED
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
0 TO 1
DIFFBULB
0 TO 1
DIFFENTH
0 TO 1
0 TO 1
FILT_AL
0 TO 1
0 TO 1
DBLOCK
0 TO 1
DST_CFG