POINT DESCRIPTION
Vent IDF Run Hours
Ventilation Fan Starts
Zone Sensor 1 Address
Zone Sensor 2 Address
Zone sensor 3 address
Zone sensor 4 address
Zone sensor 5 address
ZS Zone Temp
APPENDIX E: BACnet Points List
Analog Value (AV) Points (cont)
POINT ACCESS
UNITS
READ ONLY
hrs
READ ONLY
R/W
R/W
R/W
R/W
R/W
R/W
° F
BACnet OBJECT
BACnet ID
NAME
hour_vent_fan
AV:64
st_ventf
AV:152
zsaddr1
AV:8034
zsaddr2
AV:8035
zsaddr3
AV:8036
zsaddr4
AV:8037
zsaddr5
AV:8038
ZSZoneTemp
AV:1905
125
CCN POINT
VALUE RANGE
EQUIVALENT
0 TO 999999
HR_VENTF
0 TO 999999
ST_VENTF
0x00 TO 0xFF
ZSADDR1
0x00 TO 0xFF
ZSADDR2
0x00 TO 0xFF
ZSADDR3
0x00 TO 0xFF
ZSADDR4
0x00 TO 0xFF
ZSADDR5
--- 40 TO 245
ZSZT