Table A-2 provides the AC and DC specifications for the GT100.

Table A-2 Electrical Specifications

Specification
Nominal AC Input Voltage
(+10% to -12% acceptable range)
Maximum Continuous AC Output Current 121 A
Nominal AC Input Frequency
(+0.5 to -0.7 Hz acceptable range)
Line Power Factor
Output Power
Sell Power Range
Peak Power Tracking Window
Maximum Open Circuit Voltage
Nominal DC Voltage
Maximum DC Current
DC Current Ripple
Maximum Array Short Circuit Current
DC Back-feed Current
AC Current Distortion
Efficiency
Standby and Night-time Tare Loss
Table A-3 provides the regulatory specifications for the GT100.

Table A-3 Regulatory Specifications

Standard
General Standards
Emitted Interference
This manual for use by qualified installers only
System Specifications
GT100-480-NG and
GT100-208-NG and
GT100-480-PG
GT100-208-PG
480 Vac
208 Vac
(423 to 528 Vac)
(184 to 228 Vac)
278 A
rms
60 Hz
60 Hz
(57.0 to 60.5 Hz)
(57.0 to 60.5 Hz)
>0.99
>0.99
100 kW
100 kW
1 kW to 100 kW
1 kW to 100 kW
300 to 480 Vdc
300 to 480 Vdc
600 Vdc
600 Vdc
345 Vdc
345 Vdc
347 A
347 A
< 2% at rated power < 2% at rated power
460 A
460 A
0 A
0 A
< 5% THD at rated
< 5% THD at rated
power
power
> 96.0%
> 95.0%
< 100 W
< 100 W
Regulation Met
UL 1741 Rev 2005
UL 508C
IEEE 1547
CSA 107.1-01
IEEE Std C37.90.2-1995
FCC Class A
rms