The "Floor curing" function ensures controlled drying of the floor. It controls the flow
temperature in accordance with a certain temperature profile.
Observe the relevant standards and regulations of the company supplying the
floor!
Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
Deviations may damage the attic!
The function can be aborted prematurely by choosing Off.
Maximum limitation of the flow temperature remains active.
Off:
The function is deactivated.
Function heating (Fh):
The 1st part of the temperature profile is run automatically.
Floor curing heating (Fh):
The 2nd part of the temperature profile is run automatically.
Functional and floor curing heating
The entire temperature profile (first and second part) is traversed automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is traversed automatically.
Manual
In manual mode, no temperature profile is used. The required flow temperature
must be set individually for every heating circuit, using parameter Floor curing setp
manually.
The function is automatically ended after 25 days.
The flow temperature setpoint for the "Manual floor curing" function can be set
separately for each heating circuit.
First, start the "Floor curing" function, then adjust the setpoint manually. The start
value is 25 °C and can be manually readjusted at any time. Floor curing setp
manually (TVEm) can only be adjusted within the 2 limit values Flow temperature
setpoint maximum (TVMax) and Flow temperature setpoint minimum (TVmin).
The function ends after the function days (Fh+Bh = 25 days) expire or the function
is switched off via the parameter start day (day 0) which is not counted as a
functional day.
Displays the current day and the current setpoint of the "Floor curing" function in
progress.
User manual RVS43.345
The settings in detail
Operating line
Floor curing function
Off ¦ Functional heating ¦ Curing heating ¦ Functional/curing
heating ¦ Manually
Floor curing setp manually
Floor curing day current
Floor curing days completed