Boiler controller
Table of Contents

Advertisement

Setpoints
Room temperature.
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint max
Siemens
Building Technologies
Line no.
HC1
HC2
HC3
710
1010
1310
712
1012
1312
714
1014
1314
716
1016
1316
The setpoint setting ranges are obtained as a result of the interdependency of
setpoints. This is shown in the following graph: The individual setpoints required for
each heating circuit can be adjusted.
0
2
4
6
TRKmax
Comfort setpoint max
TRK
Comfort setpoint
TRR
reduced setpoint
TRF
Frost protection setpoint
The Comfort setpoint is the desired room temperature during normal room
occupancy (e.g. during the daytime). It is used as the setpoint when the plant
operates in Automatic mode (during the Comfort phase) and in Comfort mode.
The Reduced setpoint is the desired room temperature during reduced room
occupancy (e.g. at night or when not used for a number of hours). It is used as the
setpoint when the plant operates in Automatic mode (during the Reduced phase)
and in Reduced mode.
The frost protection setpoint is the room temperature setpoint for the periods of
time when the room is not occupied (e.g. during holidays), but protection from
extremely low temperatures shall be provided for the hydraulic system or animals
and plants, antiquities, etc.
It is used as the setpoint when the plant operates in Protection mode.
The Comfort setpoint max limits the uppermost adjustable Comfort setpoint. The
Comfort setpoint cannot be set to value that is higher than the defined value on the
corresponding room unit or operating lines.
User manual RVS43.345
The settings in detail
Operating line
Comfort setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint max
TRR
TRF
8
10
12
14
16
TRKmax
TRK
18
20
22
24
26
2358Z01
CE1U2354en_021
°C
53 / 239