Line no.
Operating line
4810
Full charging
Off ¦ Current heat request ¦ Buffer setpoint
The function full charging of buffer storage tank only switches of the released heat
generation lock, despite automatic source lock, after the buffer storage tank is fully
charged.
The function "Full charge of buffer storage tank" (line 2208) must be switched for a
full charge on the selected generation.
For activated function, the generation parameterized for the full charge function, if
the full charge setpoint is achieved, or if the boiler must be switched off based on
the burner control.
Off
The full charge function is deactivated.
Current heat request
The current heat request is used as the setpoint for full charge.
Buffer setpoint
The buffer storage tank is charged to the minimum full charge temperature
(line 4811).
Full charge is concluded as soon as the full charge sensor (line 4813) reaches the
corresponding setpoint.
User manual RVS43.345
The settings in detail
CE1U2354en_021