Burner control
Siemens
Building Technologies
3-position control and modulating UX
The actuator is controlled in PID mode. By setting the proportional band (Xp), the
integral action time (Tn) and the derivative action time (Tv), the controller can be
matched to the type of plant (controlled system). The actuator running time is also
set.
Neutral zone
For control operation, a neutral zone is used which is at +/- 1 K about the current
boiler temperature setpoint. If the boiler temperature stays in the neutral zone for
more than 16 seconds, the neutral zone becomes active and positioning pulses are
no longer delivered. As soon as the boiler temperature leaves the neutral zone
again, control is resumed. If the boiler temperature does not stay long enough in
the neutral zone, positioning pulses will also be delivered within the neutral zone.
Pins 3-position
Use
L1
Phase burner
Protective earth
N
Neutral conductor
T1
Phase Release modulating burner
T2
Release modulating burner
S3
Input burner fault
4
Input burner hours run
QX1
Air damper modulating burner =
CLOSED
FX4
Phase Air damper modulating burner =
(T6)
OPEN
QX4
Air damper modulating burner =
(T8)
OPEN
Connection modulating UX
Use
L1
Phase burner
Protective earth
N
Neutral conductor
T1
Phase Release modulating burner
T2
Release modulating burner
S3
Input burner fault
4
Input burner hours run
UX must be configured on an available Ux output.
User manual RVS43.345
The settings in detail
Socket
Connector type
B
AGP8S.07A/109
U
AGP8S.03C/109
Z
AGP8S.04C/109
Socket
Connector type
B
AGP8S.07A/109
CE1U2354en_021
155 / 239
2013-09-02