Boiler controller
Table of Contents

Advertisement

Electric immersion
heater
Electric immersion heater
operating mode
Electric immersion
heater: release
Example
Example
Example
Siemens
Building Technologies
Line no.
Operating line
5060
El imm heater optg mode
Substitute ¦ Summer ¦ Always
5061
El immersion heater release
24h/day ¦ DHW release ¦ Time program 4/DHW
5062
El immersion heater control
External thermostat ¦ DHW sensor
Substitute
The electric immersion heater is only used if the boiler delivers a fault status
message or if it has been shut down via boiler lock. This means that in normal
situations the DHW is heated by the boiler.
Summer
The electric immersion heater is used as soon as all connected heating circuits
have switched to summer operation. The DHW is again heated by the boiler as
soon as at least one of the heating circuits has switched back to heating mode. But
the electric immersion heater is also used if the boiler delivers a fault status
message or has been shut down via boiler lock.
Always
DHW is heated with the electric immersion heater throughout the year. When using
this setting, an electric immersion heater must be available. The boiler does not
charge!
24h / day
The electric immersion heater is always released, independent of time programs.
0
6
DHW release
The electric immersion heater is switched according to DHW release.
0
6
Time program 4 / DHW
For the electric immersion heater, time program 4 / DHW of the local controller is
taken into account.
0
6
User manual RVS43.345
The settings in detail
12
18
12
17
12
18
24
h
24
h
24
h
137 / 239
CE1U2354en_021
2013-09-02