Flow measurement
yield
Flow measurement yield
Sensor calibration
Siemens
Building Technologies
Line no.
Operating line
3891
Flow measurement yield
None ¦ With input H1 ¦ With input H31 Module 1 ¦ With input H31 Module 2 ¦
With input H31 Module 3 ¦ With input H31 Module 1 ¦ With input H31 Module
2 ¦ With input H31 Module 3 ¦ With input H32 Module 1 ¦ With input H32
Module 2 ¦ With input H32 Module 3 ¦ With input H3
In place of using the pulse count, the flow can also be measured with a flow sensor
(10 V or Hz) connected to one of the Hx inputs.
The parameter Flow measurement yield determines which input Hx is used to
meter flow:
None
No metering at input Hx.
With input Hx
The flow via the selected input is acquired and used for calculating the volume. The
determined volume is multiplied by the measured temperature difference and
added to line 8526 "Daily yield solar energy".
The Hx input selected here must be set in the configuration for the flow
measurement.
Line no.
Operating line
3896
Readj solar flow sensor
3897
Readj solar return sensor
Readjustment corrects imprecision to the sensor measured values.
User manual RVS43.345
The settings in detail
119 / 239
CE1U2354en_021
2013-09-02