Page 1
For control of • a 3-speed fan • two valve actuator with ACR12.34x/ALG for 4-pipe applications • a valve with an electric heater up to 2850 VA with ACR12.32x/ALG for 2-pipe applications Siemens Building Technologies CE1N3573E HVAC Products 17.08.2001...
Page 2
In standby operation, the controller is permanently set to an 8 °C heating setpoint. Adjustment is prohibited, due to the norms of individual countries. Cooling operation is not possible. 2/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products...
Page 3
P-band electric heater Positioning variable Heating output with ACR12.32x/ALG + ACR12.34x/ALG c/o activated Electric heater output with ACR12.32x/ALG Cooling output with ACR12.32x/ALG + ACR12.34x/ALG, c/o deactivated 3/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
Page 4
I in the neutral zone (control-free zone) or be switched off.The fan start from 0 to stage 1 is linked with a booster call instruction, to beginn with stage 3 for 1 s to warrent a safety start. 4/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products...
Page 5
Various settings can be made on the printed circuit board of the device using a 12 way DIP switch (see the following diagram). For changes to take effect, the device must be disconnected from the power supply. 5/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products...
Page 6
Control output for fan speed 1 / AC 230 V Control output for fan speed 2 / AC 230 V Control output for fan speed 3 / AC 230 V 6/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
Page 7
ACR12.320/ALG or ACR12.321/ALG controller Control output for electric heater Window contact, occupancy detector In N1 application, heating valve. In N2 application, cooling or heating valve (changeover) Cooling valve 7/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
‘Schrack’ Type RT214730 ( 230 VAC input ; 12 Amps/250V relais contact ). For this Recommended type a rail adapter is available (Schrack RT78625). relais type: 8/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
Changeover- or return air sensor B2 - M Inputs Voltage against earth AC 230 V Cable length max. Temperature sensor QAH11 (NTC Element) 9/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
Page 10
Product safety Automatic control devices for use in the home and similar applications EN 60730-1 Special requirements for energy controllers EN60730-2-11 Housing Colour RAL 9010 10/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
Page 11
Dimensions 3573M01 61,6 11/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...
Page 12
ã1999 Siemens Building Technologies Ltd Subject to change 12/10 Siemens Building Technologies Fan coil controller for wall mounting ACR12 CE1N3573E HVAC Products 17.08.2001...