Siemens AVS75.39 Series User Manual page 194

Boiler controller
Table of Contents

Advertisement

BX extension module
H2 to extension module
1, 2 and 3
Temperature sensor H2
194 / 239
Siemens
Building Technologies
Defines usage of the BX sensor inputs.
Line no.
Mod. 1
Mod. 2
Mod. 3
7307
7382
7457
7308
7383
7458
Refer to function descriptions, operating line "Sensor input BX1".
Line no.
Mod. 1
Mod. 2
Mod. 3
7311
7386
7461
7312
7387
7462
7314
7389
7464
7315
7390
7465
7316
7391
7466
7317
7392
7467
The settings for input H2 on the extension module correspond to a large extent to
those for the Hx inputs on the controller (without Pulse count, Flow measurement
Hz). For descriptions, refer to operating line "Function input H1, H3" and following.
Line no.
Mod. 1
Mod. 2
Mod. 3
7318
7393
7468
Defines the temperature acquired by the sensor connected to "Input H2 module
1....3" (solar flow/return or heat pump flow/return). The controller uses the acquired
temperature to control the respective plant component.
If, for temperature acquisition, the same sensor is defined at Bx and Hx, the sensor
connected to Bx is given priority.
User manual RVS43.345
The settings in detail
Operating line
Sensor input BX21 module 1, 2, 3
Sensor input BX22 module 1, 2, 3
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return
sensor B7 ¦ DHW circulation sensor B39 ¦ Buffer sensor B4 ¦
Buffer sensor B41 ¦ Flue gas temp sensor B8 ¦ Common flow
sensor B10 ¦ Solid fuel boiler sensor B22 ¦ DHW charging
sensor B36 ¦ Buffer sensor B42 ¦ Common return sensor B73
¦ Cascade return sensor B70 ¦ Swimming pool sensor B13 ¦
Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return
sensor B64 ¦ DHW outlet sensor B38 ¦ Solid fuel boil ret sens
B72
Operating line
Function input H2 module 1, 2, 3
None ¦ Optg mode change HCs+DHW ¦ Optg mode
changeover DHW ¦ Optg mode changeover HCs ¦ Optg
mode changeover HC1 ¦ Optg mode changeover HC2 ¦ Optg
mode changeover HC3 ¦ Heat gen lock ¦ Error/alarm
message ¦ Consumer request VK1 ¦ Consumer request VK2
¦ Release swi pool source heat ¦ Excess heat discharge ¦
Release swi pool solar ¦ Operating level DHW ¦ Operating
level HC1 ¦ Operating level HC2 ¦ Operating level HC3 ¦
Room thermostat HC1 ¦ Room thermostat HC2 ¦ Room
thermostat HC3 ¦ DHW flow switch ¦ Circ'pump thermostat ¦
Dewpoint monitor ¦ Flow temp setp incr hygro ¦ Boiler return
thermostat ¦ Status info suppl source ¦ Charg prio DHW sol
fuel boil ¦ Consumer request VK1 10V ¦ Consumer request
VK2 10V ¦ Pressure measurement 10V ¦ Rel room humidity
10V ¦ Room temp 10V ¦ Flow measurement 10V ¦ Temp
measurement 10V
Contact type H2 module 1, 2, 3
NC ¦ NO
Voltage value 1 H2 module 1, 2, 3
Funct value 1 H2 module 1, 2, 3
Voltage value 2 H2 module 1, 2, 3
Funct value 2 H2 module 1, 2, 3
Operating line
Temp sensor H2 module 1, 2, 3
None ¦ Solar flow sensor B63 ¦ Solar return sensor B64 ¦
CE1U2354en_021
2013-09-02