Siemens AVS75.39 Series User Manual page 172

Boiler controller
Table of Contents

Advertisement

Sensor
types/readjustments
Sensor type collector and
flue gas temperature
Readjustment
temperature sensor
Building and room
model
Example
172 / 239
Siemens
Building Technologies
Line no.
Operating line
6097
Sensor type collector
NTC ¦ Pt 1000
6098
Readjustm collector sensor
6099
Readjustm coll sensor 2
6100
Readjustm outside sensor
6101
Sensor type flue gas temp
NTC ¦ Pt 1000
6102
Readjustm flue gas sensor
Selection of type of sensor used. The controller uses the respective temperature
characteristic.
A table of the temperatures and associated resistances is available at the end of
the document under "Sensor characteristics".
The measured value of the outside temperature can be readjusted by +/- 3 K.
Line no.
Operating line
6110
Time constant building
When the outside temperature varies, the room temperature changes at different
rates, depending on the building's thermal storage capacity.
The above setting is used to adjust the response of the flow temperature setpoint
when the outside temperature varies.
> 20
Room temperature responds more slowly to outside temperature variations
10...20
This setting is suited for most types of buildings
< 10
Room temperature responds more quickly to outside temperature variations
User manual RVS43.345
The settings in detail
CE1U2354en_021
2013-09-02